DOP-3000 - Beam smoke detector

The DOP-3000 beam detector is designed to identify smoke arising in the early stage of fire. It is particularly suitable for protection of the rooms where smoke is expected in the first phase of the fire and where, due to the large area of the room, a great number of point smoke detectors should be used.

Variety 

Addressable/conventional linear smoke detector

Application

The detector can be an excellent way to protect uncomplicated rooms with a large surface area, where a larger number of point smoke detectors would need to be used. It should be used wherever smoke is expected in the first phase of a fire.

Compatibility 

The DOP-3000 detector can operate on the detection lines of fire alarm control panels directly in the addressable loops of the POLON 3000 system control panels, and so on the conventional lines of the IGNIS 1000 and IGNIS 2000 control panels and on the so-called side (conventional) lines behind the ADC-4001M adapter.

Specification:
  • Type Addressable, Conventional, line
  • Category To work in normal conditions
  • Type Smoke
  • Operational voltage 16,5 VDC - 24,6 VDC
  • Detector current consumption from an addressable line < 300 μA
  • Quiescent current consumption max. detector current consumption from conventional line 2,2 mA or 5 mA
  • Current consumption in alarm mode 20 mA
  • Detected test fires TF1 to TF5 and TF8
  • Addressing Address coding automatically from control panel
  • Operating temperature range from -25°C to 55°C
  • Relative humidity to 95% at 40°C
  • Dimensions of detector with base 84 x 129 x 80 mm
  • Weight 0.35 kg
  • Enclosure colour black/white
  • Other parameters Operating range with 4xE39-R8 reflector set - from 50 to 100 m, Operating range with E39-R8 reflector - from 5 to 50 m, Sensitivity thresholds - 18 %, 30 %, 54 %, Number of detectors on conventional line - 1, Power supply for laser sight - 6F22 9 V battery
Name File type File name File size Download
DOP-3000 Declaration of Performance Declaration of Performance DOP-3000_DWU_1_E399-1_20241-1.pdf 6.5 MB
DOP-3000 Declaration of Conformity Declaration of Conformity DOP-3000_DZ_UE_1_E399-1_20241-2.pdf 2.29 MB
DOP-3000 Certificate of Constancy of Performance Certificates DOP-3000_1438-CPR-0897-1.pdf 4.67 MB
DOP-3000 Installation and Maintenance Manual Installation and Maintenance Manual IK-E399-001-GB.pdf 1.29 MB
DOP-3000 Datasheet Datasheets KK-E399_06.2022-GB.pdf 149.41 KB