DUR-40K - Duct smoke detector

The DUR-40K duct smoke detector is designed to identify visible smoke, accompanying the occurrence of most fires, supervising the air in ventilation ducts and other ducts, where due to the cross-section of the duct, fast air movement and other factors, it is not possible to directly install the detector inside the ductThe DUR-40K detector identifies all test fires characteristic of optical detectors. It has a high sensitivity to visible and invisible smoke.

Variety

Analogue multi-sensor detector DUR-40K

Application

smoke detector is designed to identify visible smoke associated with formation of most fire types in any ventilation ducts where due to the cross-section of the duct, rapid air movement or other factors it is not possible to install detector directly in the duct

Compatibility

The PUO-35EX detectors can operate in lines/loops of the IGNIS 1000/2000 or the ADC-4001M adapter side line in POLON 4000 fire alarm control panels

Specification:
  • Type duct, conventional
  • Variety smoke
  • Operational voltage 12 VDC - 28 VDC
  • Quiescent current consumption ≤ 60 µA
  • Current consumption in alarm mode 20 mA
  • Detected test fires TF2D, TF4D and TF8D
  • Addressing conventional detector without addresses
  • Operating temperature range -25 °C to +55°C
  • Relative humidity up to 95 % at 40 °C
  • Dimensions 175 x 196 x 100 mm
  • Outlet tube length 240 mm
  • Suction tube length 240mm tube included.Optional 600mm, 900mm and 1200mm
  • Weight (without socket) < 0,95 kg
  • Other parameters Duct air velocity from 1 m/s to 20 m/s