SAB-6102 - Conventional sounder beacon

Conventional Sounder Beacon SAB-6102 are designed for acoustic and optical fire signaling in a tone. They have the ability to synchronize the emitted acoustic and optical signals within a group of signaling devices operating in one acoustic and optical space and to mute with an additional button.

Overview

Conventional Sounder Beacon SAB-6102 are designed for acoustic and optical fire signaling in a tone. They have the ability to synchronize the emitted acoustic and optical signals within a group of signaling devices operating in one acoustic and optical space and to mute with an additional button. They are designed to work with all fire alarm control panels that provide the appropriate supply voltage at their outputs.

Design

The essential part of the siren is a piezoelectric transducer used to produce an acoustic signal and an LED with a lens located on the top of the siren. The entire unit is mounted in a housing similar to the Series 40 detector. To mount the siren on the ceiling or wall, use the G-40SK socket made of flame-retardant plastic, supplied with the siren. There is a screwless terminals connector for connecting the installation wires which is placed in the socket The connector has six terminals designed to bridge the wires: two power lines, synchronize signals and mute them with an additional external switch.

Specificații:
  • Type tone, optical, acustic, low current
  • Version conventional
  • Mounting internal
  • Supply voltage 16,0 VDC ÷ 32.5 VDC
  • External power unit supply voltage 16,0 VDC ÷ 32,5V DC
  • Current consumption from external power supply ≤130 mA at the signaling mode
  • Sound level up to 105 dB
  • flashing frequency 0,5 Hz
  • flash time 0,2 s
  • Operating temperature range -25 °C to +55 °C
  • Frame IP rate IP 21C
  • Dimensions (including socket) Ф 115 x 94 mm
  • Weight (including socket) 0,26 kg