IGNIS 2500 - Automatic fire extinguishing control panel (Conventional)

The IGNIS 2500 automatic extinguishing control panel is designed for fire detection and control of fixed extinguishing devices containing extinguishing agent (gaseous, liquid or aerosol form) and monitoring the automatic extinguishing process. The IGNIS 2500 cooperate with conventional 40 series fire detectors and specialized PU-61 and PW-61 buttons, enabling manual start and stop of the extinguishing process, as well as with SE-1 and SW-1 information acoustic and visual signalling devices, as well as SG-1 and SG-2. The control panel is offered in two extinguishing versions : one- and two-zones. It can also work in a multi-zone set consisting of several control panels and a common extinguishing agent resource.

The IGNIS 2500 automatic extinguishing control panel is designed for fire detection and control of fixed extinguishing devices containing extinguishing agent (gaseous, liquid or aerosol form) and monitoring the automatic extinguishing process. IGNIS 2500A, as a subsystem, works with conventional 40 series fire detectors and dedicated PU-61 and PW-61 buttons, enabling manual start and stop of the extinguishing process, nformative acoustic signaling and optic devices SE-1 and SW-1, SG-1 and SG-2. The control panel is offered in two extinguishing versions – one zone – and two-zones. It can also work in a multi-zone set consisting of several control panels and a common extinguishing agent resource

 

NameIGNIS 2500 conventional
IGNIS 2500Single-zone control panel (non-expandable)
IGNIS 2500RSingle-zone control panel (expandable)
IGNIS 2500-2Single-zone control panel (non-expandable)
IGNIS 2500-2RDual-zone control panel (expandable)
Specificații:
  • Supply voltage (main) 230 V
  • Supply voltage (standby) 2 pcs. 12 V from 7 Ah up to 18 Ah
  • Number of conventional detection lines 2 to 6
  • Max. quiescent current in detection line 2 mA
  • Detection line resistance 2 x 120 Ω
  • Maximum number of point detectors on conventional line 32
  • Detection line termination resistor 1 kΩ
  • Signaling lines (potential) 10
  • Potential-free relay outputs in control panel 6
  • Number of detection lines up to 16
  • Number of extinguishing zones 2
  • Number of detection zones 3
  • Operating temperature range -5 °C to +40 °C