DOT-40 - Multi-sensor smoke and heat detector

The DOT-40 multi -sensor (optical smoke and heat) detector is designed for detection of a smoke and a rise in temperature concurrent with a fire at its early development stage.

Variety

Conventional, heat and smoke detector.

Application:
The DOT-40 multi -sensor (optical smoke and heat) detector is designed for detection of a smoke and a rise in temperature concurrent with a fire at its early development stage. At the time of the simultaneous detection of both the increase in temperature and smoke detector transmits an alarm signal to the fire alarm control panel. The use of two sensors eliminates the possibility of false alarms and allows the use of detectors in areas where due to the amount of dust or dirt that was not previously possible.

Compatibility:
The DOT-40 detectors can operate in  lines/loops of the IGNIS 1000 or on the side line of ADC-4001M adapter in POLON 4000 fire alarm control panels.

Specificații:
  • Type conventional, multisensor, point
  • Category Regular working conditions
  • Variety smoke and heat
  • Operational voltage 12 VDC - 28 VDC
  • Quiescent current consumption ≤ 60 µA
  • Current consumption in alarm mode 20 mA
  • Detector class A1R, A1S, BR, BS acc. to PN-EN 54-5
  • Detected test fires TF1 to TF6 as well as TF8
  • Addressing conventional detector without addresses
  • Operating temperature range -25 °C to +55 °C
  • Relative humidity up to 95 % at 40 °C
  • Dimensions of detector with base Ф115 x 71 mm
  • Weight 0.15 kg
  • Frame colour white/any colour of the RAL palette (special order only)