DOP-6001R - Beam smoke detector

The DOP-6001R beam detector is designed to detect smoke generated at an early stage of fire.It is particularly suitable for protection of the rooms where smoke is expected in the first phase of the fire, and where - due to the area of the room - a large number of point smoke detectors should be used.The DOP-6001R beam smoke detectors are equipped with fire alarm and fault relay outputs, which enable them to operate in detection lines of any fire alarm system control panels as well as in burglar alarm systems.

Variety

Beam smoke detector

Application

Detector is particularly suitable for protection of rooms where smoke is expected in the first phase of the fire, and where
, due to area of the room, a large number of point smoke detectors should be used.

Compatibility

The DOP-6001R detector can cooperate with any alarm signaling control panels, providing supply voltage in the range from 9.5 V to 28 V and current of 100 mA, its alarm signal is switching of potential-free relay contacts>

Specificații:
  • Type Beam, conventional
  • Category to work in normal conditions
  • Variety smoke
  • Operational voltage 9 VDC - 28 VDC
  • Quiescent current consumption (9,6 VDC - 28 VDC) 8 - 30 mA
  • Current consumption in alarm mode (9,6 VDC - 28 VDC) 20 - 100 mA
  • Detected test fires TF1 to TF5 and TF8
  • Operating temperature range -25 °C to +55 °C
  • Relative humidity up to 95 % at 40 °C
  • Dimensions of detector with base 84 x 128x 79 mm
  • Weight 0.35 kg
  • Frame colour black/white
  • Other parameters Range of work with the 4xE39-R8 reflector unit - 50 m up to 100 m, Range of work with the E39-R8 reflector - 5 m up to 50 m, Sensitivity thresholds - 18 %, 30 %, 54 %,Laser sight power supply - 6F22 9 V battery