The UCS 6000 universal control panel is designed to activate fire-fighting devices used for gravitational and mechanical smoke extraction (smoke ventilation dampers, shut-off dampers) and enables:
- Fire (smoke) detection;
- Activation of fire-fighting devices installed in smoke extraction systems (automatic or manual)
- Accoustic and optical device operating states signalling (alarm, fault);
- Automatic control of fire protection and actuators (actuators, electromagnets, fans, etc.) of the smoke extraction system;
- Automatic conduct of the control panel’s own systems and circuits;
- Providing basic information to main control panels (e.g. POLON 4000 , POLON 6000, POLON 3000, IGNIS 1000 or others) regarding alarms, faults, condition of fire protection and actuator equipment.
The UCS 6000 control panel can operate individually as a single or multi-zone universal smoke extraction controller or in addressable detection lines/loops of the POLON 4000 and POLON 6000 system fire alarm control panels.
Control panel modules:
MGS-60 module
- a supervised line receiving the alarm signal from an external fire alarm control panel,
- a rain and/or wind sensor supply line,
- a rain and/or wind sensor signal receiving line,
- the supervised PKA alarm relay (continuity of wire), the PKU fault relay.
MGL-60 Module
- conventional detector line (40 model range detectors),
- conventional line for manual smoke exhaust call points ( PO-6X model range manual call points),
- Control and supply universal supervised main output for fire protection devices (servomotors of fire/smoke dampers, electromagnets of fire zones separators, etc.),
- Status of limit switches control lines of fire protection devices controlled and powered by the main output,
- lines receiving signals from ventilation push buttons (OPEN, CLOSE);
MPW-60 Module:
- PK1 and PK2 high voltage type programmable relays (5 A/ 230 V)
- 2 supervised programmable LK1 and LK2 (24 V) monitoring lines;
MPD-60 module:
- 2 supervised, programmable relays PK1 and PK2 (1 A / 24 V),
- 2 supervised programmable LK1 and LK2 (24 V) monitoring lines;
MKA-60 Module :
- POLON 4000 communication line (addressable detector line);
MZU-60 Module:
- supply fault relay – PKUZ (1 A / 24 V)
- External devices supply supervised output (0.5 A / 24 V).