SAW-3001 - Adressable Accoustic Sounder

The SAW-3001 addressable sounders are designed for acoustic signaling of fire in a tone. They operate on addressable lines/loops of POLON 3000 fire alarm systems.

Purpose

The SAW-3001 addressable sounders are designed for acoustic signaling of fires in a tone manner. They operate on addressable lines/loops of POLON 3000 systems fire alarm control panels. SAW-3001 are activated at the signal sent by the control panel, when the programmed triggering criteria are met, e.g. when a fire is detected in the selected supervisory zone,

Design

The piezoelectric transducer sounder electronics are housed in a frame similar to the Series 40 detector. There is a place to put a 9V 6F22 battery in the case. To mount the siren on the ceiling or wall, use the G-40S socket made of flame retardant plastic – supplied with the siren. There is a screwless terminals connector – placed in the socket – for joining the installation wires The connector has six terminals, two pairs labeled “+” and “-” as the input and output of the detection line and two terminals for connecting an external 24 V power supply.

Specificații:
  • Type tone, acoustic, low current
  • Version addressable
  • Mounting internal
  • Supply voltage 9.6 VDC ÷ 32.0 VDC
  • Detection line operating voltage 16.5 VDC ÷ 24.6 VDC
  • External power unit supply voltage 9.6 VDC ÷ 32 VDC
  • Battery current consumption ≤150 mA in signaling state
  • Current consumption from external power supply ≤50 mA in signaling state with 24 VDC power supply
  • Current consumption from external power supply ≤100 mA in signaling state with 12 VDC power supply
  • Sound level up to 103 dB
  • Operating temperature range -25 °C to +55 °C
  • Frame IP rate IP 21C
  • Dimensions (without socket) Ф 115 x 59 mm
  • Weight (excluding socket and battery) 0.20 kg
  • Other parameters Operating time from 6LR61 batteries during alarming - min 3h,
    Surveillance operating time from 6LR61 batteries - from 2 to 5 years