IGNIS 2500A - Automatic fire extinguishing control panel (Adressable)

The IGNIS 2500 automatic extinguishing control panel is designed for fire detection and control of fixed extinguishing devices containing extinguishing agent (gaseous, liquid or aerosol form) and monitoring the automatic extinguishing process. The IGNIS 2500 cooperates with conventional 40 series fire detectors and dedicated PU-61 and PW-61 buttons, enabling manual start and stop of the extinguishing process, with SE-1 and SW-1 information acoustic and visual signalling devices and SG-1 / SG-2. The control panel is offered in two extinguishing versions - one and two-zones. It can also work in a multi-zone set consisting of several control panels and a common extinguishing agent resource.

The IGNIS 2500 automatic extinguishing control panel is designed for fire detection and control of fixed extinguishing devices containing extinguishing agent (gaseous, liquid or aerosol form) and monitoring the automatic extinguishing process. IGNIS 2500A, as a subsystem, works with conventional 40 series fire detectors and dedicated PU-61 and PW-61 buttons that enable manual start and stop of the extinguishing process. It also works with informative acoustic signaling devices and optics SE-1 and SW-1, as well as SG-1 and SG-2. The control panel is offered in two extinguishing versions – one – and two-zones. It can also work in a multi-zone set consisting of several control panels and a common extinguishing agent resource

It is an addressable version of the IGNIS 2500 control panel, designed to operate on the addressable detection loops of the POLON 6000 system.
This solution provides unique opportunities for full cooperation of the POLON 6000 system and IGNIS 2500 control panels, which then formed a extinguishing subsystem.

IGNIS 2500A, as a subsystem, works with conventional 40 series fire detectors and specialized buttons PU-61 and PW-61, enabling manual start and stop of the extinguishing process, as well as with informative acoustic signaling devices
and optics SE-1 and SW-1, as well as SG-1 and SG-2.
The control panel is offered in two extinguishing versions – one-zone and two-zone. It can also work in a multi-zone set, consisting of several control panels and a common extinguishing agent resource.

The IGNIS 2500 automatic extinguishing control panel in the addressable version is available in the following versions.

NameIGNIS 2500 conventional
IGNIS 2500ASingle-zone control panel (non-expandable)
IGNIS 2500ARSingle-zone control panel (expandable)
IGNIS 2500A-2Single-zone control panel (non-expandable)
IGNIS 2500A-2RDual-zone control panel (expandable)
Specificații:
  • Supply voltage (main) 230 V
  • Supply voltage (standby) 2 pcs. 12 V from 7 Ah up to 18 Ah
  • Number of conventional detection lines 2 to 6
  • Max. quiescent current in detection line 2 mA
  • Detection line resistance 2 x 120 Ω
  • Maximum number of point detectors in conventional line 32
  • Detection line termination resistor 1 kΩ
  • Signaling lines (potential) 10
  • Potential-free relay outputs in control panel 6
  • Number of detection lines up to 16
  • Number of extinguishing zones 2
  • Number of detection zones 3
  • Operating temperature range -5 °C to +40 °C