Autonomous gas detector CO (carbon monoxide), external DC power 9-30 V.
Autonomous ASG-2003 gas detectors range ASG-2000 are designed to detect flammable and toxic gases in hazardous locations such as garages, car parks, boiler rooms etc. When the particular threshold is exceeded, the detector’s optical indicator is activated and appropriate outputs for controlling the external sounder beacon are activated. It is also possible to start ventilation to release and remove harmful gases from the room. When the particular threshold is exceeded the detector’s optical indicator is activated and appropriate outputs for controlling the external sounder beacon are activate.
Microprocessor detector measurement systems continuously analyze the gas concentration in the room and compare it with the values of the relevant alarm thresholds. Each detector has got three alarm thresholds, strictly related to a defined gas concentration in the air. When the particular threshold is exceeded, the detector’s optical indicator is activated and appropriate outputs for controlling the external sounder beacon are activated. A failure states (detector’s failure, sensore’s failure, power failure, no sensor module) are signaled by a separate LED and a programmable relay output.
Selection of autnomous ASG-2000 detectors
Model | ASG-2001 | ASG-2001HV | ASG-2002 | ASG-2002HV | ASG-2003 | ASG-2003HV |
Detected gas | CNG (natural gas) (selective methane) | LPG (propane – butane) | CO carbon monoxide | |||
Sensor module | MSG-6001 | MSG-6002 | MSG-6003 | |||
Sensor type | semiconductor | semiconductor | electrochemical | |||
Power supply | 9 ÷ 30 V DC | 230 V AC | 9 ÷ 30 V DC | 230 V AC | 9 ÷ 30 V DC | 230 V AC |
Parameter | ASG-200x | ASG-200xHV |
Supply voltage | 9 ÷ 30 V DC | 230 V AC ± 10 % |
Power Consumption | max 120 mA / 12 Vmax 60 mA / 24 V | max 3 W |
Alarm thresholds | ASG-2001: A1 = 10 % A2 = 20 % A3 = 30 % DGW methane (selective) ASG-2002: A1 = 10 % A2 = 20 % A3 = 30 % DGW propane-butane (50 / 50) ASG-2003: A1 = 30 ppm CO (TWA 15 min.) A2 = 60 ppm CO (TWA 15 min.) A3 = 150 ppm (exceeded for at least 60 s) according to PN-EN 50545-1 | |
Working conditions | -20 ÷ 50 °C humidity. 10 ÷ 90 % | |
Storage conditions | 0 ÷ 40 °C humidity 10 ÷ 80 % | |
Protection level | IP54 (in the recommended mounting position) | |
Load capacity of relay outputs | 3 A / 30 V DC 3 A / 250 V AC Limitation of common terminal 3A (due to internal connections). |