The SAB-3006 addressable Sounder Beacon is designed for acoustic and optical fire signaling by voice. Device operates on addressable lines/loops of POLON 3000 fire alarm system.
Purpose
The SAB-3006 addressable Sounder Beacon is designed for acoustic and optical fire signaling by voice. It operates on addressable lines/loops of POLON 3000 fire alarm systems. Device is activated at the signal sent by the control panel when the programmed triggering criteria are met, e.g. when a fire is detected in the selected detection zone, general alarm in the control panel.
For proper operation the component requires two supply voltages simultaneously:
– From the detection line
– From an external power supply.
Design
The essential part of the siren is a piezoelectric transducer used to produce an acoustic signal and an LED with a lens located on the top of the siren. The entire unit is mounted in a housing similar to the Series 40 detector. To mount the siren on the ceiling or wall, use the G-40S socket made of flame retardant plastic – supplied with the siren. There is a screwless terminals connector – placed in the socket – for joining the installation wires The connector has six terminals, two pairs labeled “+” and “-” as the input and output of the detection line and two terminals for connecting an external 24 V power supply.