banner

DUT-6046 - Heat and smoke detector

The DUT-6046 addressable multi-sensor smoke and heat detector is designed to detect the initial stage of fire during which smoke and/or temperature rise occurs.It is characterized by a significant resistance to the influence of air movement and pressure changes. The application of a dual smoke detection system (in the IR and UV range) and a dual heat detection system provides increased resistance to false alarms caused by e.g. water vapour and dust, while maintaining small dimensions and high aesthetics of the detector.

Variety

addressable, multisensor, point smoke and temperature detector

Application

The detector is designed to identify the initial stage of fire development, during which smoke appears and/or there is an increase in temperature. It is characterized by significant resistance to the influence of air movement and pressure changes.

Compatibility

Detectors can operate with an addressable lines/loops of POLON 3000/4000/6000 fire alarm control panels only.

specifikáció:
  • Type addressable, point
  • Category to work in normal conditions
  • Variety smoke and heat
  • Operational voltage 16,5 VDC - 24,6 VDC
  • Quiescent current consumption ≤ 150 µA
  • Detected test fires TF1 to TF9
  • Addressing Automatic address encoding from the control panel
  • Operating temperature range -25 °C to 50 °C
  • Relative humidity up to 95 % at 40 °C
  • Dimensions of detector with base ø 115 x 61 mm
  • Weight 0,2 kg
  • Frame colour white/any colour of the RAL palette (special order only)